LUNA2000-5_10_15-S0

  Smart Strings ESS

SCALABLE CONFIGURATION, EASY INSTALLATION, SMART AND FRIENDLY, ECONOMIC AND RELIABLE
GET QUOTE

LUNA2000 – 200/161/129KWH-2H1 LUNA2000 – 97KWH-1H1 Smart String ESS

Technical Specification LUNA2000-5-S0 LUNA2000-10-S0 LUNA2000-15-S0
Number of power modules 1
Battery module LUNA2000-5-E0
Battery module capacity

 

5 kWh
Battery usable capacity1

 

1 2 3
Peak output power 3.5 kW, 10s 7 kW, 10s 7 kW, 10s
Nominal voltage (single-phase system) 450 V
Operating voltage range (single-phase system) 350–560 V
Nominal voltage (three-phase system) 600 V
Operating voltage range (three phase system) 600–980 V
Communication
Display SOC status indicator, LED indicator
Communication RS485/CAN (only for parallel operation)
General Specification
Dimensions (W x D x H) 670 mm x 150 mm x 600 mm (26.4 in. x 5.9 in. x 23.6 in.) 670 mm x 150 mm x 960 mm (26.4 in. x 5.9 in. x 37.8 in.) 670 mm x 150 mm x 1320 mm (26.4 in. x 5.9 in. x 60.0 in.)
Weight (Floor stand toolkit included) 63.8 kg (140.7 lb) 113.8 kg (250.9 lb) 163.8 kg (361.1 lb)
Power module dimension (W x D x H)3 670 mm x 150 mm x 240 mm (26.4 in. x 5.9 in. x 9.4 in.)
Power module weight 12 kg (26.5 lb)
Battery module dimensions (W x D x H) 670 mm x 150 mm x 360 mm (26.4 in. x 5.9 in. x 14.0 in.)
Battery module weight Installation
Operating temperature –20°C to +55°C (–4°F to +131°F) 3
Max. operating altitude 4,000 m (13,123 ft.) (Derated above 2,000 m)
Environment Outdoor/Indoor 4
Relative humidity 5%–95% RH
Cooling Natural convection
IP rating IP 66
Noise emission5 < 29 dB
Cell technology Lithium-iron phosphate (LiFePO4)
Compatible inverters6 SUN2000-2/3/3.68/4/4.6/5/6KTL-L1, SUN2000-8/10K-LC0 SUN2000-3/4/5/6/8/10KTL-M1, SUN2000-12/15/17/20/25K-MB0 SUN2000-5/6/8/10/12K-MAP0, SUN5000-8/12K-MAP0, SUN5000-17/25K-MB0
Standards Compliance (More Available Upon Request)
Certificates CE, RCM, CEC, VDE2510-50, IEC62619, IEC 60730, UN38.3
Ordering and Deliverable Part
Available for ordering7 LUNA2000-5KW-C0, LUNA2000-5-E0, LUNA2000 Wall Mounting Bracket

*1 Test conditions: 100% depth of discharge (DoD), 0.2C rate charge & discharge at 25°C, at the beginning of life. If no PV modules are installed or the system has not detected sunlight for at least 24 hours, the minimum end-of-discharge SOC is 15%. *2 The weight of the battery modules varies with products, with a tolerance of ±3%. *3 Refer to battery warranty letter for conditional application. *4 Outdoor installation is recommended. For indoor installation, refer to the user manual for instruction. *5 Noise level (typical): < 29 dB(A) @1 m, 30°C, power on and run stably for 2 hours *6 Please contact a local engineer for compatibility information. *7 The power module and battery modules of the storage system are separately ordered in the required quantity.

 

Disclaimer: The preceding values are measured by an internal laboratory of Huawei in a specific environment. The actual values may vary with products, software versions, usage conditions, and environmental factors.

Click the button below to Download the Technical Specification Document

Download